Determining islanding operation using micro grid phasor measurement unit parameters

For improving the reliability of the micro grid network, a robust islanding detection algorithm is required. For creating a vigorous islanding detection algorithm voltage angle and current angle should be detected appropriately from the grid. The main objective of this research is to determine and c...

Full description

Saved in:
Bibliographic Details
Main Authors: Arefin, A.A., Hasan, K.N.M., Romlie, M.F., Abdullah, M.F., Ali, M.N., Othman, M.L.
Format: Article
Published: World Academy of Research in Science and Engineering 2020
Online Access:https://www.scopus.com/inward/record.uri?eid=2-s2.0-85092664735&doi=10.30534%2fijeter%2f2020%2f1581.12020&partnerID=40&md5=6adcdfb030444f2969cfee8df6ecffc3
http://eprints.utp.edu.my/23263/
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:For improving the reliability of the micro grid network, a robust islanding detection algorithm is required. For creating a vigorous islanding detection algorithm voltage angle and current angle should be detected appropriately from the grid. The main objective of this research is to determine and compare the voltage angle and current angle with normal operation and islanding operationof the micro grid to develop multilevel islanding detection algorithm to ensure the higher reliability. In this work, IEEE 30 bus network phasor measurement unit parameters have been determined in PowerWorldSimulator. The result shows that the proposed methodology can appropriately determine the islanding event and the comparative study shows an incredible change in phasor measurement unit parameters when grid goes on islanding operation. © 2020, World Academy of Research in Science and Engineering. All rights reserved.