Evaluation of thermal comfort in a test room equipped with a photovoltaic assisted thermo-electric air duct cooling system

This study investigates the comfort performance of a test room equipped with the south-facing photovoltaic wall (PV-W) and north-facing thermo-electric air duct (TE-AD) system for the tropical climate. Both subjective and objective measurements were used to analyze the TE-AD system cooling performan...

Full description

Saved in:
Bibliographic Details
Main Authors: Irshad, K., Habib, K., Kareem, M.W., Basrawi, F., Saha, B.B.
Format: Article
Published: Elsevier Ltd 2017
Online Access:https://www.scopus.com/inward/record.uri?eid=2-s2.0-85028363102&doi=10.1016%2fj.ijhydene.2017.05.247&partnerID=40&md5=ff8c5d9e264b4659b20b589db3f98ce8
http://eprints.utp.edu.my/19303/
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:This study investigates the comfort performance of a test room equipped with the south-facing photovoltaic wall (PV-W) and north-facing thermo-electric air duct (TE-AD) system for the tropical climate. Both subjective and objective measurements were used to analyze the TE-AD system cooling performance when operated at variable input current supply (2–7 A) from a PV system. Indoor radiant and air temperatures, relative humidity, and air velocity were measured based on ISO 7730 for objective measurement. For subjective measurement, forty respondents were required to fill up the questionnaire that developed based on UNI EN ISO 10551 and UNI EN ISO 7730 guidelines in order to access their thermal comfort opinion. The results show that the thermal response of respondents associated with indoor situation of the test room have changed from (+1) slightly warm to cool (−2) when the input current supply rises from 2 A to 6 A. The overall predicted mean vote, predicted percentage dissatisfied indices, and acceptability vote shows that more than 90 of the respondents were thermally satisfied. Integration of the PV-W system with the TE-AD system increases the thermal comfort and reduces the thermal load of the test room with other benefits includes less fuel and energy consumption, high reliability, and less maintenance operation. © 2017 Hydrogen Energy Publications LLC