Condition based monitoring of gapless surge arrester using electrical and thermal parameters

A new method to assess the condition of metal-oxide surge arresters is presented. The thermal image and third harmonic leakage current are used as an indicator. The correlation between the leakage current and temperature of the arrester is processed using a neural network. The temperature profile of...

Full description

Saved in:
Bibliographic Details
Main Authors: Novizon, Novizon, Malek, Z. A., Syafii, Syafii, Ahmad, M. H., Aulia, Aulia, Ulfiah, S. A.
Format: Conference or Workshop Item
Language:English
Published: 2019
Subjects:
Online Access:http://eprints.utm.my/id/eprint/90648/1/ZulkurnainAbdulMalek2019_ConditionBasedMonitoringofGapless.pdf
http://eprints.utm.my/id/eprint/90648/
http://dx.doi.org/10.1088/1757-899X/602/1/012007
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:A new method to assess the condition of metal-oxide surge arresters is presented. The thermal image and third harmonic leakage current are used as an indicator. The correlation between the leakage current and temperature of the arrester is processed using a neural network. The temperature profile of arrester, ambient temperature and humidity were as input to the neural network and the peak value of the third harmonic resistive current as a target. Results are presented with the training of neural network close to the target and testing result is 98% successfully.