Overcurrent relays coordination in interconnected networks using accurate analytical method and based on determination of fault critical point

Overcurrent relays should be coordinated for different operation conditions in interconnected networks. In addition, the time interval should not reach under the predefined threshold for each pair of primary and backup relays for the faults occurring in the protection zone of the primary relay. An a...

Full description

Saved in:
Bibliographic Details
Main Authors: Alkaran, Davood Solati, Vatani, Mohammad Reza, Sanjari, Mohammad Javad, Gharehpetian, Gevork B., Mohammed Yatim, Abdul Halim
Format: Article
Published: Institute of Electrical and Electronics Engineers Inc. 2015
Subjects:
Online Access:http://eprints.utm.my/id/eprint/58741/
http://dx.doi.org/10.1109/TPWRD.2014.2330767
Tags: Add Tag
No Tags, Be the first to tag this record!