Transient Analysis of Current Transformers

The objective of the present work is to investigate the performance and transient behavior of conventional electromagnetic current transformers in comparison to the unconventional current transducers during power system faults. The research has been carried out using PSPICE simulation tools and exp...

Full description

Saved in:
Bibliographic Details
Main Author: Ghumman, Muhammad Ramzan
Format: Thesis
Language:English
English
Published: 2001
Subjects:
Online Access:http://psasir.upm.edu.my/id/eprint/10986/1/FK_2001_18.pdf
http://psasir.upm.edu.my/id/eprint/10986/
Tags: Add Tag
No Tags, Be the first to tag this record!
id my.upm.eprints.10986
record_format eprints
spelling my.upm.eprints.109862024-05-14T08:57:53Z http://psasir.upm.edu.my/id/eprint/10986/ Transient Analysis of Current Transformers Ghumman, Muhammad Ramzan The objective of the present work is to investigate the performance and transient behavior of conventional electromagnetic current transformers in comparison to the unconventional current transducers during power system faults. The research has been carried out using PSPICE simulation tools and experimental testing of current transducers. Different types of transducers considered in this research include normal electromagnetic current transformers (EMCT) and its various types, Hall effect current transformers (HECT) and Opto-couplers. The simulation results have shown that electromagnetic current transformers (EMCT) can suffer from transient saturation during high frequency disturbances or permanent saturation during high fault currents. The electromagnetic current transformers (EMCT) were found to saturate above 20 kHz current surges whilst the Hall effect current transducers (HECT) were found to work up to several 100 kHz. The transformation capability of opto-coupler current transducers, using LED/Si based opto-coupler, was found to be more than 1 MHz. It was estimated that a laser and avalanche photo-detector (APD) based magnetooptic current transformer (MOCT) could effectively translate 1 GHz frequency surges. The simulation results have been experimentally tested and found to be correct within the accuracy resolution of available test and measurement equipment. Based on this work it is safe to declare that EMCT can be used for normal monitoring and measurement applications in utility. It is not good for the reliable protection and control application. Anyway, it does not compete the alternate options such as HECT and MOCT in protection and control applications regarding bandwidth, rise time and fault current diagnostics. 2001-10 Thesis NonPeerReviewed text en http://psasir.upm.edu.my/id/eprint/10986/1/FK_2001_18.pdf Ghumman, Muhammad Ramzan (2001) Transient Analysis of Current Transformers. Masters thesis, Universiti Putra Malaysia. Electric transformers Electric circuit analysis English
institution Universiti Putra Malaysia
building UPM Library
collection Institutional Repository
continent Asia
country Malaysia
content_provider Universiti Putra Malaysia
content_source UPM Institutional Repository
url_provider http://psasir.upm.edu.my/
language English
English
topic Electric transformers
Electric circuit analysis
spellingShingle Electric transformers
Electric circuit analysis
Ghumman, Muhammad Ramzan
Transient Analysis of Current Transformers
description The objective of the present work is to investigate the performance and transient behavior of conventional electromagnetic current transformers in comparison to the unconventional current transducers during power system faults. The research has been carried out using PSPICE simulation tools and experimental testing of current transducers. Different types of transducers considered in this research include normal electromagnetic current transformers (EMCT) and its various types, Hall effect current transformers (HECT) and Opto-couplers. The simulation results have shown that electromagnetic current transformers (EMCT) can suffer from transient saturation during high frequency disturbances or permanent saturation during high fault currents. The electromagnetic current transformers (EMCT) were found to saturate above 20 kHz current surges whilst the Hall effect current transducers (HECT) were found to work up to several 100 kHz. The transformation capability of opto-coupler current transducers, using LED/Si based opto-coupler, was found to be more than 1 MHz. It was estimated that a laser and avalanche photo-detector (APD) based magnetooptic current transformer (MOCT) could effectively translate 1 GHz frequency surges. The simulation results have been experimentally tested and found to be correct within the accuracy resolution of available test and measurement equipment. Based on this work it is safe to declare that EMCT can be used for normal monitoring and measurement applications in utility. It is not good for the reliable protection and control application. Anyway, it does not compete the alternate options such as HECT and MOCT in protection and control applications regarding bandwidth, rise time and fault current diagnostics.
format Thesis
author Ghumman, Muhammad Ramzan
author_facet Ghumman, Muhammad Ramzan
author_sort Ghumman, Muhammad Ramzan
title Transient Analysis of Current Transformers
title_short Transient Analysis of Current Transformers
title_full Transient Analysis of Current Transformers
title_fullStr Transient Analysis of Current Transformers
title_full_unstemmed Transient Analysis of Current Transformers
title_sort transient analysis of current transformers
publishDate 2001
url http://psasir.upm.edu.my/id/eprint/10986/1/FK_2001_18.pdf
http://psasir.upm.edu.my/id/eprint/10986/
_version_ 1800093747034193920
score 13.18916