Condition assessment of OLTC using duval triangle and static winding resistance test

On Load Tap Changer (OLTC) failure occurs is due to the insulation degradation and contacts failure inside it. Other than that, contacts wear influences the OLTC performances. The worn contacts will cause hotspots in the OLTC tank and cause the insulating oil to degrade faster. As a result, this wil...

Full description

Saved in:
Bibliographic Details
Main Authors: Khiar M.S.A., Thayoob Y.H.Md., Ghazali Y.Z.Y., Ghani S.A., Chairul I.S.
Other Authors: 55336341600
Format: Conference Paper
Published: 2023
Subjects:
Tags: Add Tag
No Tags, Be the first to tag this record!
id my.uniten.dspace-30307
record_format dspace
spelling my.uniten.dspace-303072024-04-18T11:05:33Z Condition assessment of OLTC using duval triangle and static winding resistance test Khiar M.S.A. Thayoob Y.H.Md. Ghazali Y.Z.Y. Ghani S.A. Chairul I.S. 55336341600 6505876050 55336569600 56504019900 55336864500 Contact resistance Dissolved Gas Analysis (DGA) Duval Triangle Method OLTC Static Winding Resistance Test Contact resistance Degradation Optimization Bad contact Condition assessments Dissolved gas analysis Duval Triangle Method Hotspots Insulation degradation OLTC On-load tap changers Winding resistances Engineering research On Load Tap Changer (OLTC) failure occurs is due to the insulation degradation and contacts failure inside it. Other than that, contacts wear influences the OLTC performances. The worn contacts will cause hotspots in the OLTC tank and cause the insulating oil to degrade faster. As a result, this will lead to the damage of complete transformer unit. Thus, the research work that has been carried out applied the Dissolved Gas Analysis (DGA) via latest Duval Triangle method during the diagnosis of OLTC at the first stage to provide early indication of OLTC's breakdown. The Static Winding Resistance Test is then applied at the second stage to figure out any increase of contact resistances for all phases. The capability of Static Winding Resistance Test in order to provide any sign of bad contacts in fixed condition can be done by comparing two different conditions which are before and after maintenance. � 2012 IEEE. Final 2023-12-29T07:46:32Z 2023-12-29T07:46:32Z 2012 Conference Paper 10.1109/PEOCO.2012.6230903 2-s2.0-84865018391 https://www.scopus.com/inward/record.uri?eid=2-s2.0-84865018391&doi=10.1109%2fPEOCO.2012.6230903&partnerID=40&md5=2e2311490cf74275aee30a71f470da5a https://irepository.uniten.edu.my/handle/123456789/30307 6230903 432 435 Scopus
institution Universiti Tenaga Nasional
building UNITEN Library
collection Institutional Repository
continent Asia
country Malaysia
content_provider Universiti Tenaga Nasional
content_source UNITEN Institutional Repository
url_provider http://dspace.uniten.edu.my/
topic Contact resistance
Dissolved Gas Analysis (DGA)
Duval Triangle Method
OLTC
Static Winding Resistance Test
Contact resistance
Degradation
Optimization
Bad contact
Condition assessments
Dissolved gas analysis
Duval Triangle Method
Hotspots
Insulation degradation
OLTC
On-load tap changers
Winding resistances
Engineering research
spellingShingle Contact resistance
Dissolved Gas Analysis (DGA)
Duval Triangle Method
OLTC
Static Winding Resistance Test
Contact resistance
Degradation
Optimization
Bad contact
Condition assessments
Dissolved gas analysis
Duval Triangle Method
Hotspots
Insulation degradation
OLTC
On-load tap changers
Winding resistances
Engineering research
Khiar M.S.A.
Thayoob Y.H.Md.
Ghazali Y.Z.Y.
Ghani S.A.
Chairul I.S.
Condition assessment of OLTC using duval triangle and static winding resistance test
description On Load Tap Changer (OLTC) failure occurs is due to the insulation degradation and contacts failure inside it. Other than that, contacts wear influences the OLTC performances. The worn contacts will cause hotspots in the OLTC tank and cause the insulating oil to degrade faster. As a result, this will lead to the damage of complete transformer unit. Thus, the research work that has been carried out applied the Dissolved Gas Analysis (DGA) via latest Duval Triangle method during the diagnosis of OLTC at the first stage to provide early indication of OLTC's breakdown. The Static Winding Resistance Test is then applied at the second stage to figure out any increase of contact resistances for all phases. The capability of Static Winding Resistance Test in order to provide any sign of bad contacts in fixed condition can be done by comparing two different conditions which are before and after maintenance. � 2012 IEEE.
author2 55336341600
author_facet 55336341600
Khiar M.S.A.
Thayoob Y.H.Md.
Ghazali Y.Z.Y.
Ghani S.A.
Chairul I.S.
format Conference Paper
author Khiar M.S.A.
Thayoob Y.H.Md.
Ghazali Y.Z.Y.
Ghani S.A.
Chairul I.S.
author_sort Khiar M.S.A.
title Condition assessment of OLTC using duval triangle and static winding resistance test
title_short Condition assessment of OLTC using duval triangle and static winding resistance test
title_full Condition assessment of OLTC using duval triangle and static winding resistance test
title_fullStr Condition assessment of OLTC using duval triangle and static winding resistance test
title_full_unstemmed Condition assessment of OLTC using duval triangle and static winding resistance test
title_sort condition assessment of oltc using duval triangle and static winding resistance test
publishDate 2023
_version_ 1806427602120867840
score 13.222552