Corona fault detection in switchgear with extreme learning machine

Switchgear is a very important component in a power distribution line. Failure in switchgear can lead to catastrophic danger and losses. In this research, a fault detection system is proposed with the implementation of Extreme Learning Machine (ELM). This algorithm is capable to identify faults in s...

Full description

Saved in:
Bibliographic Details
Main Authors: Ishak S., Koh S.-P., Tan J.-D., Tiong S.-K., Chen C.-P.
Other Authors: 57194057526
Format: Article
Published: Institute of Advanced Engineering and Science 2023
Tags: Add Tag
No Tags, Be the first to tag this record!
Description
Summary:Switchgear is a very important component in a power distribution line. Failure in switchgear can lead to catastrophic danger and losses. In this research, a fault detection system is proposed with the implementation of Extreme Learning Machine (ELM). This algorithm is capable to identify faults in switchgear by analyzing the sound wave generated. Experiments are carried out to investigate the performance of the developed algorithm in identifying Corona faults in switchgears. The performances are analyzed in time and frequency domains, respectively. In time domain analysis, the results show 90.63%, 87.5%, and 87.5% of success rates in differentiating the Corona and non-Corona cases in training, validation and testing phases respectively. In frequency domain analysis, the results show 89.84%, 83.33%, and 87.5% success rates in training, validation and testing phases respectively. It can thus be concluded that the developed algorithm performed well in identifying Corona faults in switchgears. � 2020, Institute of Advanced Engineering and Science. All rights reserved.