An effective islanding detection method for photovoltaic grid connected inverter / Ku Nurul Edhura Ku Ahamad
Presently, available international standard related to anti-islanding requirements on medium and low grid connected system required that voltage utility distribution network should be automatically disconnected from the distribution grid when the circuit breaker supplying the feeder connected to...
Saved in:
Main Author: | |
---|---|
Format: | Thesis |
Published: |
2013
|
Subjects: | |
Online Access: | http://studentsrepo.um.edu.my/8615/4/An_Effective_Islanding_Detection_Method_For_Photovoltaic_Grid_Connected_Inverter__Ku_Nurul_Edhura_KGA100042.pdf http://studentsrepo.um.edu.my/8615/ |
Tags: |
Add Tag
No Tags, Be the first to tag this record!
|
Summary: | Presently, available international standard related to anti-islanding requirements on
medium and low grid connected system required that voltage utility distribution network
should be automatically disconnected from the distribution grid when the circuit breaker
supplying the feeder connected to the distribution generation trips. Islanding is undesired
because it may endanger maintenance service workers and damage load equipment
through unsynchronized re-closure. In principle, the main idea of islanding is monitoring
the changes in the output parameter of the inverters or other system parameters in
indicating islanding.
This thesis presented a low cost and effective passive anti-islanding detection method
for single-phase photovoltaic grid-connected inverters. An analog circuit for over/under
voltage protection is developed to ensure fast detection and no delay to system. An under-
/over frequency circuit is also developed, for accurate and fast frequency detection with
minimal external components. A new algorithm is developed in a low cost PIC18F4550.
An improved disconnection time in the proposed method compared with that in the previously
developed method is an attractive solution for single phase grid connected inverters.
The low cost, effective and minimal external component count are the advantages.
A prototype is developed and tested to demonstrate the performance and feasibility of the
proposed method. The test was conducted on different combination of resistive, capacitive
and inductive loads. The experiment results verified that the proposed anti-islanding
detection method is able to detect islanding operation effectively under various load types,
inverter output powers and quality factors. |
---|