Neutral Earthing Impedance Design in Mitigating Third Harmonic Current At The Generator Neutral

Third harmonic (TH) is a component of triplen harmonic which is a type of waveform distortion originated from non-linear loads and synchronous generator. TH current from synchronous generator returns to its neutral via cable capacitance or other neutral grounding points in the network has caused the...

詳細記述

保存先:
書誌詳細
第一著者: Abd Rahman, Hadam
フォーマット: Final Year Project
言語:English
出版事項: IRC 2016
主題:
オンライン・アクセス:http://utpedia.utp.edu.my/17190/1/Dissertation%20hadam.pdf
http://utpedia.utp.edu.my/17190/
タグ: タグ追加
タグなし, このレコードへの初めてのタグを付けませんか!
その他の書誌記述
要約:Third harmonic (TH) is a component of triplen harmonic which is a type of waveform distortion originated from non-linear loads and synchronous generator. TH current from synchronous generator returns to its neutral via cable capacitance or other neutral grounding points in the network has caused the Neutral Earthing Resistor (NER) to experience high temperature. One of the solutions to mitigate the TH current is to use a suitable design of Neutral Earthing Impedance (NEI). In this project, the commonly used NEI device namely NER and Neutral Earthing Reactance (NERX) are being studied. Universiti Teknologi PETRONAS (UTP) distribution system is modelled in MATLAB Simulink in order to simulate the flow of TH current within the system under normal steady state condition. Once verified, grounding methods including different NEI types and several grounding configuration are applied to the developed model and the resulting behaviour of TH current for each methods and configuration is analyses.